Door and Roller Shutter Fire Resistance Test Furnace

The Door and Roller Shutter Fire Resistance Test Furnace is designed to evaluate the fire performance of doors and roller shutters installed in vertical partition openings. It is suitable for hinged doors, pivot doors, horizontal sliding doors, vertical sliding doors (including linked sliding doors and sectional doors), roller shutters, other sliding, folding, tilting doors, and movable wall-integrated panels. The furnace meets GB/T7633-2008 requirements and is intended for fire resistance testing of non-load-bearing horizontal doors and roller shutters.
Applications
(1) Fire resistance testing of hinged, pivot, sliding, folding, and tilting doors in residential, commercial, and industrial buildings.
(2) Fire performance evaluation of roller shutters in industrial and commercial environments.
(3) Fire testing of movable panels and specialized wall-integrated doors for non-load-bearing applications.
(4) Product development, quality control, and certification for door and roller shutter manufacturers targeting export markets.
(5) Research and verification for fire safety engineering projects, ensuring compliance with international fire regulations.
(6) Evaluation of building components’ compliance with NFPA, ISO, ASTM, EN, and BS fire safety standards.
Standards
(1) GB/T7633-2008 “Fire Resistance Test Method for Building Doors and Shutters”
(2) ISO 834-1:1999 “Fire Resistance Tests – Elements of Building Construction – Part 1: General Requirements”
(3) EN 1634-1:2014 “Fire Resistance and Smoke Control Tests for Door and Shutter Assemblies”
(4) ASTM E119-20 “Standard Test Methods for Fire Tests of Building Construction and Materials”
(5) BS 476 Part 22:1987 “Fire Tests on Building Materials and Structures – Methods for Determination of Fire Resistance of Non-Loadbearing Elements”
(6) NFPA 252:2020 “Standard Methods of Fire Tests of Door Assemblies”
Technical Parameters
| Parameter | Value/Specification | Notes |
|---|---|---|
| Working voltage | AC380V ±10%, 50Hz | — |
| Power consumption | 6 kW | — |
| Furnace size | 3.0m (L) × 3.0m (H) × 1.25m (D) | — |
| Maximum furnace temperature | 1250℃ | — |
| Gas supply | Propane/LPG, 50kg × 6 cylinders | — |
| Furnace pressure measurement | 0–100 Pa | Accuracy ≤ ±3 Pa |
| Airflow | 0–50 m³/min | Accuracy ≤ ±0.5 m³/min |
| Sample back-face radiation | 0–10 W/cm² | — |
| Test temperature program | 15min: ambient
~718℃ 30min: ambient ~821℃ 60min: ambient ~925℃ 90min: ambient ~986℃ 120min: ambient ~1029℃ 180min: ambient ~1115℃ 240min: ambient ~1150℃ | Programmed temperature ramp |
| Furnace temperature accuracy | ±15℃ | — |
| Sample internal temperature accuracy | ±10℃ | — |
| Sample back-face temperature accuracy | ±4℃ | — |
| Thermocouples | Furnace: 9 K-type armored,
Class II Back-face: 29 K-type armored, Class II | — |
| Timer range | 0–240 min | Accuracy < ±1 s |
| Equipment footprint | 3.8 × 2.4 × 4.5 m | — |
| Equipment weight | 4500 kg | Onsite installation required |
| Vaporization system | 150 kg/h | Optional |
Features
(1) Steel frame furnace structure with refractory brick lining and high-temperature insulation (density >1000 kg/m³).
(2) High-speed burners embedded in side walls (8 burners total) providing uniform heat distribution.
(3) Three exhaust ports at the rear connected to a flue for smoke and pressure control.
(4) Four observation windows for flame monitoring.
(5) Back-face and internal thermocouples for precise temperature measurement.
(6) T-shaped probe for furnace pressure measurement, accuracy ±2 Pa.
(7) Movable sample thermocouples for flexible positioning.
(8) Load device: 4.3m × 3.5m pushcart with 3.5m × 3.5m steel platform, movable on rails; sample lifted by hoist (customer-supplied).
(9) Gas system: two-stage pressure reducer with gas-liquid separator and eight solenoid valves.
(10) Integrated control system: MCGS configuration software with PLC, including main interface, furnace temperature curves, sample temperature display, historical records, and parameter settings.
FAQ
(1) Can the furnace test custom-sized doors and roller shutters?
Yes, special dimensions can be customized according to customer requirements.
(2) Is the hoist included for sample loading?
No, the electric hoist is not included and must be supplied by the customer.
(3) What type of gas is used in the furnace?
Propane or liquefied petroleum gas (LPG) is used, with proper safety measures.
(4) Can test data be recorded and exported?
Yes, the integrated control system supports real-time monitoring, recording, and export for reporting purposes.
(5) What is the maximum furnace temperature?
The furnace can reach up to 1250℃.
(6) How is the back-face temperature measured?
Back-face temperature is measured with 29 K-type armored thermocouples installed at standardized positions.